Power Generation Technology ›› 2017, Vol. 38 ›› Issue (5): 66-68.DOI: 10.3969/J.ISSN.2095-3429.2017.05.016
Previous Articles Next Articles
WANG Yongqiang, MAO Qingbo, LIU Shifu, GONG Xiuzhong, ZHANG Chao
Received:
Published:
Online:
Abstract: An accident of generator trip caused by over temperature of excitation transformer which run through the UNITROL 5000 excitation system had been in-troduced in this paper.According to the protection action and the recorded data, through the comprehensive inspec-tion, it is concluded that the fundamental cause of the acci-dent is the sampling distortion of the temperature measure-ment element in the excitation transformer, and the indirect reason is that the temperature protection configuration of the excitation transformer is not reasonable.
Key words: excitation transformer, over temperature, temperature protection
CLC Number:
TM76
WANG Yongqiang, MAO Qingbo, LIU Shifu, GONG Xiuzhong, ZHANG Chao. Analysis of One Generator-tripping Accident Caused by Over Temperature of Excitation Transformer[J]. Power Generation Technology, 2017, 38(5): 66-68.