Power Generation Technology ›› 2024, Vol. 45 ›› Issue (1): 79-89.DOI: 10.12096/j.2096-4528.pgt.22094

• Power Generation and Environmental Protection • Previous Articles     Next Articles

Experimental Study on the Influence of Air Side Equalizing Device on the Flow Heat Transfer Characteristics of Cooling Delta Unit

Tao GUO1, Haiyang YU1, Haibo FENG2, Hanchuan YUAN2, Bing TIAN1, Yujie YANG3, Yuanbin ZHAO4, Qian ZHAO4   

  1. 1.Guodian Zheneng Ningdong Power Generation Co. , Ltd. , Yinchuan 750408, Ningxia Hui Autonomous Region, China
    2.CHN Energy Shanghai Engineering & Technology Co. , Ltd. , Putuo District, Shanghai 200062, China
    3.Jinan Lanchen Energy Technology Co. , Ltd. , Jinan 250101, Shandong Province, China
    4.School of Energy and Power Engineering, Shandong University, Jinan 250061, Shandong Province, China
  • Received:2023-09-13 Published:2024-02-29 Online:2024-02-29
  • Contact: Yuanbin ZHAO
  • Supported by:
    the National Natural Science Foundation of China(51606112);Science and Technology Innovation Capability Improvement Project of Medium-Sized Enterprises in Shandong Province(2022TSGC1026);Sci-Tech Innovation Project of China Energy Ningxia Power Electric Co., Ltd(NXDL-2022-28)

Abstract:

For the cooling delta unit, the basic heat transfer element of the cold end of the indirect air-cooling system, the wind speed, air temperature, and wall temperature measuring points were arranged laterally along the heat transfer bundle in the cooling columns on both sides of cooling delta with or without air equalizing apparatus. The wall temperature measuring points were further arranged on the left and right side of water outlet cooling columns. The changes of lateral windward wind speed, wind temperature, wall temperature and outlet water temperature of the cooling columns on both sides along the heat transfer bundles were compared and analyzed. And the influence mechanisms of the air equalizing apparatus on the flow and heat transfer characteristics of the cooling delta unit and the outlet water temperature were studied. The results show that, with the air equalizing apparatus, the distribution of lateral windward wind speed and wall temperature of the two sides cooling columns are more uniform along the heat transfer bundle.

Key words: coal-fired power unit, indirect air-cooling system, cooling delta, air side equalizing device, flow heat transfer, water temperature distribution