Experiment on Multi-Component Synchronous Test of Reducing Atmosphere Adjacent to Water Wall of High Temperature Corrosion Boiler
Power Generation Technology Vol. 44, Issue 6, Pages: 800-808(2023)
Power Generation and Environmental Protection|Updated:2025-06-06
|
Experiment on Multi-Component Synchronous Test of Reducing Atmosphere Adjacent to Water Wall of High Temperature Corrosion Boiler
- “On a 300 MW high-temperature corrosion boiler, it was found that there is a positive correlation between CO concentration and H2S, H2 concentration, and a negative correlation with CO2 concentration. As the furnace height increases, the positive correlation between CO and H2S weakens.”
DOI:10.12096/j.2096-4528.pgt.23009
Scan QR Code
53
Views
175
Downloads
0
CSCD
Alert me when the article has been cited
Submit
Related Articles
Research on Slagging and High Temperature Corrosion Prevention and Control of a 1 000 MW Ultra Supercritical Double Tangentially Fired Boiler
Multi-Objective Prediction Model for Combustion State of Biomass Circulating Fluidized Bed Boiler Based on Multi-Scale Feature Fusion Enhanced Neural Network
Analysis of Influence of Flue Gas Recirculation on Thermodynamic Performance and Economic Efficiency of 125 MW Supercritical CO2 Coal-Fired Power Generation Unit
Experimental Study on Wide-Load Low-NOx Combustion Retrofit for Circulating Fluidized Bed Boiler Burning High-Alkali Coal
Optimization Method of Flow Field for Alleviating Clogging of Mist Eliminator in Desulfurization Tower
Related Author
ZHANG Haijun
CHENG Jian
ZHONG Yuxiu
XU Jun
JIANG Long
WANG Yi
SU Sheng
HU Song
Related Institution
CHN Energy Hanchuan Power Generation Co., Ltd., Hanchuan
State Key Laboratory of Coal Combustion, Huazhong University of Science and Technology
CHN Energy Changyuan Electric Power Co., Ltd.
School of Electric Power Engineering, South China University of Technology
Guangdong Yudean Zhanjiang Biomass Power Co., Ltd.