基于循环水泵变频的1 000 MW超超临界机组冷端综合优化
张东青, 金铁铮, 张磊

Comprehensive Optimization of the Cold End of 1 000 MW Ultra-Supercritical Unit Based on Pump Frequency Conversion
Dongqing ZHANG, Tiezheng JIN, Lei ZHANG
表7 宁海1 000 MW机组循环水泵工频运行与变频优化煤耗率对比
Tab. 7 Comparison of coal consumption rate of Ninghai 1 000 MW unit with constant frequency operation and frequency conversion optimization of circulating water pump
日期环境温度/℃环境湿度/%煤耗率/[g/(kW∙h)]
100%负荷75%负荷50%负荷
变频优化工频运行变频优化工频运行变频优化工频运行
01.01—01.157.855.5294.2301.2*289.0298.3*295.9303.4*
01.16—01.317.067.5293.9301.5*289.0298.5*295.9303.4*
02.01—02.145.549.3294.5308.5*289.7308.5*296.1311.4*
02.15—02.289.868.6293.7296.9288.8292.8296.0298.6
03.01—03.1514.559.3293.4293.8288.9292.2297.0299.1
03.16—03.3114.962.6293.4296.2289.0291.6297.3299.0
04.01—04.1519.256.0293.5294.1289.7290.2299.5300.1
04.16—04.3021.454.2293.8293.9290.4290.5301.2301.5
05.01—05.1524.356.9294.8295.0292.0292.5304.4305.6
05.16—05.3125.466.6295.7295.8293.6293.9307.1307.9
06.01—06.1525.162.2295.3295.4293.1293.3306.5307.0
06.16—06.3028.763.1297.6297.5296.2296.2311.0311.4
07.01—07.1530.960.5298.9298.8298.0298.0313.5313.6
07.16—07.3131.459.4299.1299.0298.4298.3314.2314.1
08.01—08.1531.460.1299.2299.2298.5298.4314.3314.2
08.16—08.3130.959.5298.7298.6297.9297.8313.5313.4
09.01—09.1528.261.5297.1297.2295.5295.4310.0309.6
09.16—09.3026.561.9296.0296.1294.0294.0307.9307.5
10.01—10.1521.154.5293.9293.9290.4290.5301.2301.3
10.16—10.3119.158.0293.6294.1289.7290.2299.7300.1
11.01—11.1517.069.9293.5294.4289.5290.3298.9299.6
11.16—11.3014.471.1293.4296.0289.0291.5297.5299.0
12.01—12.1511.470.3293.5300.8*288.8295.5*296.4300.5*
12.16—12.3110.362.0293.5304.1*288.8299.7*296.0303.0*