基于循环水泵变频的1 000 MW超超临界机组冷端综合优化
张东青, 金铁铮, 张磊

Comprehensive Optimization of the Cold End of 1 000 MW Ultra-Supercritical Unit Based on Pump Frequency Conversion
Dongqing ZHANG, Tiezheng JIN, Lei ZHANG
表6 宁海1 000 MW机组最佳运行背压和循环水量
Tab. 6 Optimal operating back pressure and circulating water flow of Ninghai 1 000 MW unit
日期环境温度/℃环境湿度/%100%负荷75%负荷50%负荷
最佳背压/kPa循环水量/(t/h)最佳背压/kPa循环水量/(t/h)最佳背压/kPa循环水量/(t/h)
01.01—01.157.855.54.7/8.336 0003.5/5.436 0002.7/3.935 000
01.16—01.317.067.54.5/7.838 0003.5/5.538 0002.6/3.737 000
02.01—02.145.549.34.2/7.438 0003.4/5.634 0002.5/3.733 000
02.15—02.289.868.64.7/7.842 0003.7/5.642 0002.8/3.942 000
03.01—03.1514.559.34.8/7.550 0004.0/5.750 0003.2/4.150 000
03.16—03.3114.962.64.8/7.455 0004.0/5.555 0003.2/4.153 000
04.01—04.1519.256.05.2/7.465 0004.4/5.962 0003.6/4.560 000
04.16—04.3021.454.25.4/7.473 0004.6/5.970 0003.9/4.768 000
05.01—05.1524.356.95.9/7.883 0005.1/6.480 0004.3/5.178 000
05.16—05.3125.466.66.3/8.290 0005.4/6.788 0004.7/5.587 000
06.01—06.1525.162.26.0/7.793 0005.2/6.492 0004.5/5.292 000
06.16—06.3028.763.16.9/8.894 0006.0/7.393 0005.3/6.193 000
07.01—07.1530.960.57.3/9.297 0006.4/7.797 0005.6/6.497 000
07.16—07.3131.459.47.4/9.2100 0006.5/7.8100 0005.7/6.5100 000
08.01—08.1531.460.17.4/9.3100 0006.5/7.8100 0005.7/6.5100 000
08.16—08.3130.959.59.0/7.2100 0006.4/7.6100 0005.6/6.4100 000
09.01—09.1528.261.56.7/8.695 0005.9/7.195 0005.1/5.995 000
09.16—09.3026.561.96.4/8.292 0005.5/6.792 0004.8/5.591 000
10.01—10.1521.154.55.2/7.083 0004.5/5.683 0003.8/4.581 000
10.16—10.3119.158.05.1/6.970 0004.3/5.670 0003.6/4.369 000
11.01—11.1517.069.95.1/7.463 0004.3/5.860 0003.5/4.458 000
11.16—11.3014.471.15.0/7.653 0004.0/5.753 0003.3/4.251 000
12.01—12.1511.470.34.6/7.250 0003.8/5.745 0003.0/4.045 000
12.16—12.3110.362.04.6/7.445 0003.7/5.543 0002.8/3.843 000