基于循环水泵变频的1 000 MW超超临界机组冷端综合优化
|
张东青, 金铁铮, 张磊
|
Comprehensive Optimization of the Cold End of 1 000 MW Ultra-Supercritical Unit Based on Pump Frequency Conversion
|
Dongqing ZHANG, Tiezheng JIN, Lei ZHANG
|
|
表5 2机4泵运行时循环水泵变频和运行方式对耗功的影响
|
Tab. 5 Influence of frequency conversion and operation mode on water pump power consumption when 2 units and 4 pumps are running
|
|
循环水流量/(t/h) | 2机4定频泵 | 2机2变频泵2定频泵 | 2机4变频泵 |
---|
功耗/kW | 功耗/kW | 变频比 | 功耗/kW | 变频比 |
---|
66 000 | — | — | — | 5 301 | 0.805 | 68 000 | — | — | — | 5 501 | 0.814 | 70 000 | 9 552 | 6 813 | 0.754 | 5 708 | 0.824 | 72 000 | 9 611 | 6 958 | 0.771 | 5 934 | 0.834 | 74 000 | 9 670 | 7 117 | 0.788 | 6 170 | 0.845 | 76 000 | 9 723 | 7 279 | 0.803 | 6 411 | 0.856 | 78 000 | 9 773 | 7 447 | 0.818 | 6 665 | 0.866 | 80 000 | 9 804 | 7 615 | 0.831 | 6 927 | 0.877 | 82 000 | 9 836 | 7 781 | 0.842 | 7 198 | 0.888 | 84 000 | 9 865 | 7 960 | 0.853 | 7 488 | 0.900 | 86 000 | 9 897 | 8 145 | 0.863 | 7 788 | 0.911 | 88 000 | 9 911 | 8 339 | 0.874 | 8 092 | 0.923 | 90 000 | 9 928 | 8 557 | 0.888 | 9 412 | 0.934 | 92 000 | 9 942 | 8 796 | 0.905 | 8 745 | 0.946 | 94 000 | 9 959 | 9 062 | 0.924 | 9 092 | 0.958 | 96 000 | 9 977 | 9 361 | 0.946 | 9 454 | 0.971 | 98 000 | 10 000 | 9 688 | 0.968 | 9 823 | 0.983 | 100 000 | 10 009 | 10 049 | 0.992 | 10 205 | 0.996 |
|
|
|