基于循环水泵变频的1 000 MW超超临界机组冷端综合优化
张东青, 金铁铮, 张磊

Comprehensive Optimization of the Cold End of 1 000 MW Ultra-Supercritical Unit Based on Pump Frequency Conversion
Dongqing ZHANG, Tiezheng JIN, Lei ZHANG
表3 2机2泵运行时循环水泵变频和运行方式对耗功的影响
Tab. 3 Influence of frequency conversion and operation mode on water pump power consumption when 2 units and 2 pumps are running
循环水流量/(t/h)2机2定频泵

2机1变频泵

1定频泵

2机2变频泵
功耗/kW功耗/kW变频比功耗/kW变频比
42 0002 6400.800
44 0002 8100.815
46 0002 9920.833
48 0004 9883 2560.7583 1830.851
50 0005 0053 4040.7823 3850.870
52 0005 0173 5750.8093 5980.890
54 0005 0233 7690.8393 8210.909
56 0005 0093 8950.8714 0530.930
58 0004 9664 2180.9064 2930.950
60 0004 9034 4630.9424 5410.970
62 0004 8284 7220.9794 7980.989
64 0004 8624 9981.0005 0681.000