Study on Low Reheat Steam Temperature After Low NOx Retrofit Based on Combustion Adjustment

Shenglin HU1(),Yuan LI1(),Rui MAO1,Shengping ZHAN1,Liming REN1,Zhicheng GUO1,Kefa CEN2   

  1. 1 Rundian Energy Science and Technology Co., Ltd., Zhengzhou 450042, Henan Province, China
    2 State Key Laboratory of Clean Energy Utilization(Zhejiang University), Hangzhou 310027, Zhejiang Province, China
  • Received:2019-05-22 Published:2019-10-30 Online:2019-11-05
  • Supported by:
    国家自然科学基金创新研究群体项目(51621005)

Abstract:

To solve the problem of low reheat steam temperature after low NOx retrofit in a 330 MW coal-fired boiler, the countermeasure study was conducted based on combustion adjustment strategies. The effects of burner angle, air distribution mode, burner layer distribution, coal type of upper layer, coal fineness of upper layer, ash blowing of horizontal flue, and automatic control quality on reheat steam temperature were analyzed. The results indicate that the low reheat steam temperature mainly occurs at medium-low load (lower than 250 MW). Increasing burner angle, using inverted tower air distribution, increasing utilization rate of upper burner, improving coal calorific of upper layer, decreasing coal fineness of upper layer, strengthening ash blowing of horizontal flue and optimizing automatic control quality are conducive to improving the reheat steam temperature. The proposed combustion adjustment strategies provide important reference for the similar problem in boiler retrofit.

Key words: coal-fired boiler, low NOx retrofit, reheat steam temperature, combustion adjustment